                   GENERAL TERMS AND CONDITIONS OF SERVICE
                                 (Continued)

2.  QUALITY OF GAS  

    2.1   Quality Standards:  The gas which Shipper delivers hereunder to 
          NBP for transport (and the gas which NBP transports hereunder for 
          Shipper) shall be merchantable gas at all times complying with the 
          following quality requirements:

          (a)   Heating Value:  The gas shall have a Gross Heating Value of 
                not less than nine hundred ninety (990) and not greater than 
                one thousand one hundred fifty (1150) Btus per standard 
                cubic foot on a dry basis, but with the consent of Shipper, 
                NBP may deliver gas at a lower Gross Heating Value.

          (b)   Gas Quality (at the pressure and temperature at which the 
                gas is delivered):  The gas:

                (i)    Shall be commercially free from sand, dust, gums, 
                       crude oil, impurities and other objectionable 
                       substances.

                 (ii)  Shall not have a hydrocarbon dew-point in excess of 
                       twenty degrees (20 o) Fahrenheit at pressures up to 
                       six hundred (600) psig.

                (iii)  Shall not contain more than one-quarter (1/4) grain of 
                       hydrogen sulfide per one hundred (100) standard cubic 
                       feet.

                 (iv)  Shall not contain more than three-quarters (0.75) 
                       grain of total sulphur per one hundred (100) standard 
                       cubic feet. 

                 (v)   Shall not contain more than two percent (2%) by volume 
                       of carbon dioxide.

                 (vi)  Shall not contain more than three percent (3%) total 
                       diluents (the total combined carbon dioxide, nitrogen, 
                       helium, oxygen, and any other diluent compound) by 
                       volume.

                (vii)  Shall not contain more than seven (7) pounds of water 
                       vapor per one million (1,000,000) standard cubic feet.